The ADC-4001M adapter works in detector lines/loops of the POLON 4000 control panels. It is designed to transfer information about the status of the detector line connected to the adapter, so called ‘side line’ (conventional), as well as about the status of the POLON-ALFA produced non-addressable double-status 30 or 40 model range detectors installed in thisline.
The ADC-4001M unit also enables the following:
The ADC-4001M adapter is installed in the G-40 base.
Operation voltage | 16.5V -24V |
Max side line load current (at choice) | 0.15mA or 0.3mA or 1mA or 2mA |
Max side line resistance | max 2 x 25 Ohm |
Operating temperature | from -25°C to 55°C |
Dimensions (without base) (mm) | Ø 115 x 133 |
Weight | 0.13kg |